HEATING ELEMENTS MADE OF FINNED PIPES - WELDED IN ARCS - TYPE RAO

RAO 32x2x92

Type RAO 32x2x92 2/1 2/2 2/3 2/4
Dimension (h x l) 200x1000 200x2000 200x3000 200x4000
Capacity (W) Water 90/70oC 835 1496 2308 3130
Forced steam 50 kPa 1248 2240 3452 4684
Surface (m2) 2,38 5,34 8,24 11,18
Weight (kg) 13 25 35 47

RAO 57x3x137

Type RAO 57x3x137 2/1 2/2 2/3 2/4
Dimension (h x l) 280x1040 280x2040 280x3040 280x4040
Capacity (W) Water 90/70oC 990 2190 3422 4630
Forced steam 50 kPa 1492 3326 5154 6960
Surface (m2) 3,6 7,9 12,3 16,7
Weight (kg) 19,5 40 59,5 80

RAO 76x3x156

Type RAO 76x3x156 2/1 2/2 2/3 2/4 2/5 2/6
Dimension (h x l) 350x1080 350x2080 350x3080 350x4080 350x5080 350x6080
Capacity (W) Water 90/70oC 1003 2200 3422 4626 5846 6960
Forced steam 50 kPa 1550 3331 5154 6955 8799 10475
Surface (m2) 3,7 8 12,3 16,6 21 25
Weight (kg) 22,6 45 67,9 88,5 113,4 135

RAO 32x2x92

Type RAO 32x2x92 3/1 3/2 3/3 3/4
Dimension (h x l) 300x1000 300x2000 300x3000 300x4000
Capacity (W) Water 90/70oC 1252 2243 3460 4693
Forced steam 50 kPa 1870 3358 5176 7024
Surface (m2) 4,52 8,05 12,41 16,81
Weight (kg) 20 37 53 71

RAO 57x3x137

Type RAO 57x3x137 3/1 3/2 3/3 3/4
Dimension (h x l) 430x1080 430x2080 430x3080 430x4080
Capacity (W) Water 90/70oC 1494 3295 5178 6944
Forced steam 50 kPa 2238 5020 7751 10485
Surface (m2) 5,4 11,9 18,5 25,1
Weight (kg) 28 60 90 120

RAO 76x3x156

Type RAO 76x3x156 3/1 3/2 3/3 3/4 3/5 3/6
Dimension (h x l) 550x1160 550x2160 550x3160 550x4160 550x5160 550x6160
Capacity (W) Water 90/70oC 1503 3300 5178 6939 8769 10496
Forced steam 50 kPa 2304 5028 7751 10475 13198 15712
Surface (m2) 5,5 12 18,5 25 31,5 37,5
Weight (kg) 32,6 66,5 100,1 130 167 197,6

RAO 32x2x92

Type RAO 32x2x92 4/1 4/2 4/3 4/4
Dimension (h x l) 400x1000 400x2000 400x3000 400x4000
Capacity (W) Water 90/70oC 1665 2989 4613 6257
Forced steam 50 kPa 2493 4477 6901 9365
Surface (m2) 6,01 10,71 16,52 22,41
Weight (kg) 26 49 71 95

RAO 57x3x137

Type RAO 57x3x137 4/1 4/2 4/3 4/4
Dimension (h x l) 580x1080 580x2080 580x3080 580x4080
Capacity (W) Water 90/70oC 1992 4476 6844 9257
Forced steam 50 kPa 2985 6665 10349 13982
Surface (m2) 7,3 15,9 24,7 33,4
Weight (kg) 39 80 120 161

RAO 76x3x156

Type RAO 76x3x156 4/1 4/2 4/3 4/4 4/5 4/6
Dimension (h x l) 750x1160 750x2160 750x3160 750x4160 750x5160 750x6160
Capacity (W) Water 90/70oC 2004 4481 6844 9252 11692 13995
Forced steam 50 kPa 3142 6704 10349 13952 17597 20949
Surface (m2) 7,5 16 24,7 33,3 42 50
Weight (kg) 41 86 132 174 223 270

The diameters of connection outlets or other modifications of the heating elements are to be made upon
the customer's wish.

Back to the listing of products.

 

2002 © RADIANA-KOVO spol. s  r.o.